sinee — Chapter 11 Function Code Table

User Manual of EM760 High-Performance Inverter 325 F14.39 Speed integral time constant ASR T2 _ 0.000~30.000 0.000: no integral s 0.300 ● 0x0E27 F14.40 Switching frequency 1 0.00 to switching frequency 2 Hz 5.00 ● 0x0E28 F14.41 Switching frequency 2 Switching frequency 1 to maximum frequency F00.16 Hz 10.00 ● 0x0E29 F14.42 No-load current gain of motor 2 10.0~300.0 % 100.0 ● 0x0E2A F14.43 Filtering time constant of speed loop output 0.000~0.100 s 0.001 ● 0x0E2B F14.44 Vector control slip gain 50.00~200.00 % 100.00 ● 0x0E2C F14.45 Upper limit source selection of speed control torque 0: Set by F14.46 and F14.47 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5:

Communication setting (percentage) 6: Take the maximum values of AI2 and AI3 7: Take the minimum values of AI2 and AI3 0 O 0x0E2D F14.46 Upper limit of speed control motor torque 0.0~250.0 % 165.0 ● 0x0E2E F14.47 Upper limit of speed control brake torque 0.0~250.0 % 165.0 ● 0x0E2F F14.48 Excitation current proportional gain ACR-P1 0.00~100.00 0.50 ● 0x0E30 F14.49 Excitation current integral time constant ACR-T1 0.00~600.00 0.00: no integral ms 10.00 ● 0x0E31 F14.50 Torque current proportional gain ACR-P2 0.00~100.00 0.50 ● 0x0E32 F14.51 Torque current integral time constant ACR-T2 0.00~600.00 0.00: no integral ms 10.00 ● 0x0E33