User Manual of EM760 High-Performance Inverter 340 F18.41 View any address 0 × 0x1229 F18.42 Random carrier frequency display 1000~16000 HZ 0 × 0x122A F18.51 PID output -100.0~100.0 % × 0x1233 F18.58 Feedback pulse high 0~65535 0 × 0x123A F18.59 Feedback pulse low 0~65535 0 × 0x123B F18.60 Inverter temperature -40~200 ℃ 0 × 0x123C F18.67 Saved electric energy (MWH) Cumulative energy saving MWH MWh 0~65535 × 0x1243 F18.68 Saved electric energy (KWH) Cumulative energy saving KWH kWh 0.0~999.9 × 0x1244 F18.69 Saved electric charge (1,000 yuan) High cumulative cost saving (*1000) 0~65535 × 0x1245 F18.70 Saved electric charge (yuan) Low cumulative cost saving 0.0~ 999.9 × 0x1246 F18.71 Power-frequency power consumption MWh Power-frequency power consumption MWH MWh 0~65535 × 0x1247 F18.72 Power-frequency power consumption KWh Power-frequency power consumption KWH kWh 0.0~999.9 × 0x1248 F19 Fault record group F19.00 Last fault category 0:
No failure Refer to Chapter 6 “Faults and Solutions” for fault codes. 0 × 0x1300 F19.01 Output frequency in failure 0.00 to upper frequency limit Hz 0.00 × 0x1301 F19.02 Output current in failure 0.00 to 650.00 (rated power ofmotor: ≤75 kW) 0.0 to 6500.0 (rated power of motor: > 75 kW) A 0.00 × 0x1302 F19.03 Bus voltage in failure 0~1200 V 0 × 0x1303