sinee — 6.1.2 Start/stop via terminal control

User Manual of EM760 High-Performance Inverter Chapter 6 Application function description 6.1 Running command The command source is used to specify the input methods for start-up, stop, forwarding, reversing, jogging and other commands for inverter control. There are three ways for the command source, i.e. keyboard control, terminal control, and communication control. The final command source also relates to the input functions “24: switching from the Run command to keyboard” and “25: switching from the Run command to communication”; If the input function “24: switching from the Run command to keyboard” is valid, the current command source is “keyboard control”. Ifthe input function “25:

switching from the Run command to communication” is valid, the current command source is “communication control”. Otherwise, the command source depends on the setting ofthe function code F00.02. 6.1.1 Start/stop via keyboard control Set the parameter F00.02=0: keyboard control. on the keyboard. In the case of no trip protection, press the RUN key The start and stop of the inverter are controlled by the RUN key , STOP key to enter the running status. If the green LED indicator between the RUN key is ON, it indicates that the inverter is in the running status. If this indicator is flickering, it means that the inverter is in the status of deceleration to stop.

and the M.K key Regardless ofthe speed or torque reference input control, the inverter will run in the input control mode at the jog speed once jogging is enabled. 6.1.2 Start/stop via terminal control F00.02=1: terminal control The start and stop of the inverter are controlled by the start and stop control terminals that are defined by the function codes F02.00 to F02.13. Detailed settings of terminal control are dependent on F00.03. Terminal RUN: Xi terminal is set to “1: terminal RUN” Terminal F/R: Xi terminal is set to “2: running direction F/R” Terminal control can be divided into two types: two-line control and three-line control. Two-line control:

73 Function code Function code name Parameter description Unit Default setting Attribute F00.02 Options of command source 0: keyboard control 1: Terminal control 2: Communication control 0 〇 Function code Function code name Parameter description Unit Default setting Attribute F00.03 Options of terminal control mode 0: terminal RUN (running) and F/R (forward/reverse) 1: terminal RUN (forward) and F/R (reverse) 2: terminal RUN (forward), Xi (stop) and F/R (reverse) 3: terminal RUN (running), Xi (stop) and F/R (forward/reverse) 0 〇