User Manual of EM760 High-Performance Inverter 6.2.2.3 Setting main frequency via high-speed pulses (HDI) (1) Set F00.06=0 (main frequency setting) (2) Set F00.04=5 (high-speed pulse setting) (3) Set F02.06=40 (the X7 function is for high-speed pulse input) (4) Set the given corresponding offset curve in F02.26~F02.29. See 6.5.3 for details. (5) High-speed pulse 100% corresponds to F00.16 (maximum frequency). Upon inputting pulses of certain frequency atX7, you can check current frequency setting via F18.01.
6.2.2.4 Setting main frequency via communication (1) Set F00.06=0 (main frequency setting) (2) For a slave of master-slave communication, set F00.04=6 ( communication percentage setting ofmain frequency ), F10.05=1 (master-slave communication enabled),and F10.06=0 (slave), and the main frequency source A is set to “700FH (master-slave communication setting) * F00.16 (maximum frequency) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%. (3) For a slave other than those of master-slave communication with the master setting in percentage, set F00.04=6 (percentage setting and F10.05=0 (master-slave communication disabled).
The main frequency source A is set to “7001H (communication percentage setting of the main channel frequency A) * F00.16 (maximum frequency)”; data range of 7001H: - 100.00%~100.00%. (4) For a slave other than those of master-slave communication with direct setting frequency for master setting, set F00.04=7 (percentage setting). The main frequency source A is set to “7015H (communication setting of the main channel frequency A)”; data range of 7015H: 0.00~F00.16 (maximum frequency). (5) Select communication address, baud rate and format in F10.00~F10.02. (6) With the frequency set for the master, you can check ifthe set frequency is correct via F18.01.
6.2.2.5 Setting main frequency via multi-segment speed Multi-segment speed has the top priority in main frequency setting. The final set frequency is determined by multi-segment speed terminals 1 - 4. If all of the multi-segment speed terminals 1 - 4 are not working, the main frequency is determined as per the main frequency source set by F00.04 and the state of DI terminals No. 51 - 56.
Table 6-2 Combination of Multi-segment Speed Command and Multi-segment Speed Terminal 81 Segment Speed Multi- segment speed terminal 4 Multi- segment speed terminal 3 Multi- segment speed terminal 2 Multi- segment speed terminal 1 Selected frequency Corresponding function code 1 Invalid Invalid Invalid Invalid Main frequency determined by F00.04 and DI terminals No. 51 - 56 F00.04