4-2 Function Mode Frequency Conversion Coefficient This function displays a conversion value obtained by multiplying the Inverter output frequency by the coefficient set in [b086]. This helps display the actual physical value on the monitor. Displayed value [d007] = "Output frequency [d001]" Ч "Frequency conversion coefficient [b086]" 4 (Display) [d007] 0.00 to 99.99 : Displays in increments of 0.01. 100.0 to 999.9 : Displays in increments of 0.1. 1000. to 9999. : Displays in increments of 1. 1000 to 3996 : Displays in increments of 10. Functions (Setting range) [b086] 0.1 to 99.9: 0. : Can be set in increments of 1.
(Example) When the output frequency [d001] = 50.0 Hz, and the frequency conversion coefficient [b086] = 1.1, the monitor [d007] displays "55.0" through 50.0 Ч 1.1 = 55.0. STOP Key Selection •You can select whether to enable the STOP key on the Digital Operator, even if the RUN command is set to the control terminal block (terminal). •The trip reset function via the STOP/RESET key works according to this setting. Free-run Stop Selection and Stop Selection Activating the free-run stop (FRS) function shuts off the Inverter output, letting the motor go into free-run status. •Helps stop the motor using a mechanical brake such as an electromagnetic one.
4-35 Function code Item Data Default setting Unit b086 Frequency conversion coefficient 0.1 to 99.9 1.0 Related functions d007 Parameter No. Function name Data Default setting Unit b087 STOP key selection 00: Enabled 01: Disabled 00 Parameter No. Function name Data Default setting Unit b088 Free-run stop selection 00: 0 Hz start 01: Frequency pull-in restart 00 b091 Stop selection 00: Deceleration → Stop 01: Free-run stop 00 b003 Retry wait time 0.3 to 100.0 1.0 s Related functions C001 to C006