Appendix-1 Parameter List Appendix * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. App-11 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value Initialization b084 Initialization selection 00: Clears the trip monitor 01: Initializes data 02: Clears the trip monitor and initializes data 00 No b085 Initialization parameter selection 00 * Do not change. 00 No Others b086 Frequency conversion coefficient 0.1 to 99.9 1.0 Yes b087 STOP key selection 00: Enabled 01: Disabled 00 No b088 Free-run stop selection 00: 0 Hz start 01:
Frequency pull-in restart 00 No b090 Usage rate of regenerative braking function 0.0 to 100.0 0.0 No % b091 Stop selection 00: Deceleration → Stop 01: Free-run stop 00 No b092 Cooling fan control 00: Always ON 01: ON during RUN 02: Depends on the fin temperature 01 No b095 Regenerative braking function operation selection 00: Disabled 01: Enable (Disable during stop) 02: Enable (Enable during stop) 0.0 No b096 Regenerative braking function ON level 200-V class: 330 to 380 400-V class: 660 to 760 200-V class: 360 V 400-V class: 720 V No V b130 Overvoltage LAD stop function 00: Disabled 01: Enabled 00 No b131 Overvoltage LAD stop function level setting 200-V class: 330. to 395.
400-V class: 660. to 790. 200-V class: 380 V 400-V class: 760 V Yes V b140 Overcurrent suppression function 00: Disabled 01: Enabled 00 No b150 Automatic carrier reduction 00: Disabled 01: Enabled 00 No b151 Ready function selection 00: Disabled 01: Enabled 00 No