omron — Precautions for Use

2-1 Installation „ Installation Environment •Increased ambient temperatures will shorten the life of the Inverter. •Keep the Inverter away from heating elements (such as a braking resistor, DC reactor, etc.). If the Inverter is installed in a control panel, keep the ambient temperature within the range of the specifications, taking dimensions and ventilation into consideration. 2 Design •If the ambient temperature is from 40 ° C to 50 ° C, the carrier frequency should be reduced and the Inverter capacity should be increased. •Before installing the Inverter, place a cover over all the ventilation openings to shield them from foreign objects.

After completing the installation process, be sure to remove the covers from the Inverter before operation. Control circuit terminal block A Control circuit terminal block B Top cover Main circuit terminal block Relay output terminal block 2-4 10 cm min. 5 cm min. 5 cm min. 10 cm min. 10 cm min. 5 cm min. 5 cm min. 10 cm min. Airflow Wall