omron — Wiring the Control Circuit Terminals and Relay Output Terminals

2-3 Wiring Wiring the Control Circuit Terminals and Relay Output Terminals Relay 2 Control circuit terminal block A Relay output terminal block Control circuit terminal block B FS FC AM PC P1 P2 MB FV FI MA MC Design Relay output „ Wiring Example of the Control Circuit Terminal Block (Sink Logic) External power supply terminal for input signal At sink logic (NPN): External power supply input 2-step acceleration/ deceleration Multi-step speed reference 2 Multi-step speed reference 1 Input common Reverse RUN command Forward RUN command At source logic (PNP): Power supply output Reset Note:

By factory default, the input logic of the multi-function input terminal circuit is set to the sink logic. SC S6 S5 S4 S3 S2 S1 PSC FS FC AM PC Variable resistor 2 3 1 Frequency meter Frequency reference (1 to 2 k Ω ) 1k Signal during RUN Frequency arrival signal 27 V DC 50 mA max. Note 1: When connecting a relay to the multi-function output terminal, install a surge-absorbing diode in parallel with the relay. The output circuit can break down due to surge voltage when the relay is switched on/off. Note 2: For the signal line, use a twisted shield wire and apply the shield coating as illustrated on the next page. Keep the length to 20 m or less. 2-13 SC S6 S5 S4 S3 S2 S1 PSC FV FI P1 Y R