omron — Wiring the Main Circuit Terminals

2-3 Wiring Screw Tightening Torque 2 Design „ Explanation of the Main Circuit Terminal Connection * Terminal symbols for 3G3MX-AE ††† are indicated as L1, L2, N/L3 instead of R/L1, S/L2, T/L3 respectively. „ Main Circuit Connection Diagram Molded case circuit-breaker (MCCB) MC AC reactor noise filter Fuse Regenerative braking unit R/L1 P/+2 N/- U/T1 V/T2 M Power supply S/L2 T/L3 * W/T3 Inverter 3G3MX * Terminal symbols for 3G3MX-AE ††† are indicated as L1, L2, N/L3 instead of R/L1, S/L2, T/L3 respectively. 2-17 Screw Tightening torque M2 0.2 N•m (max. 0.25 N•m) M2.5 0.5 N•m (max. 0.6 N•m) M3.5 0.8 N•m (max. 0.9 N•m) M4 1.2 N•m (max. 1.3 N•m) M5 2.0 N•m (max.

2.6 N•m) Control Circuit Terminal Block SC S6 S5 S4 S3 S2 S1 PSC SC S6 S5 S4 S3 S2 S1 FS FV FI FCAM PC P2 P1 Relay output terminal block MB MA MC FS FV FI FC AM PC P 2 P1 MB MA MC Terminal symbol Terminal name Function Connection example R/L1, S/L2, T/L3 * Main power supply input terminal Connect the input power supply. Motor ELB Power supply Do not remove the short-circuit bar between +1 and P/+2 when a DC reactor is not connected. U/T1, V/T2, W/T3 Inverter output terminal Connect to the motor. +1, P/+2 External DC reactor terminal Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and P/+2 when a DC reactor is connected.

P/+2 RB External braking resistor connection terminal Connect the optional braking resistor. (If a braking torque is required) P/+2, N/- Regenerative braking unit connection terminal Connect optional regenerative braking units. (If a braking torque is required) (if insufficient with only the built-in braking circuit) Ground terminal Ground (Connect to the ground to prevent electric shock and reduce noise.) Motor ELB Power supply