omron — Wiring the Main Circuit Terminals

2-3 Wiring *1. Below are the contact specifications of the relay outputs. 2 Design „ Mode Selector For the mounting position of each selector, refer to page 1-6. Available to switch the input logic (source or sink) in the multi-function input terminal circuit. Select the mode according to the option connected to the communications connector. When using the 3G3AX-OP01 supplied with the Inverter, it is available regardless of the switch condition. 2-24 Output terminal Resistance load Inductive load MA-MC Max. contact capacity 250 V AC, 2 A 30 V DC, 3 A 250 V AC, 0.2 A 30 V DC, 0.6 A Min. contact capacity 100 V AC, 10 mA 5 V DC, 100 mA MB-MC Max.

contact capacity 250 V AC, 1 A 30 V DC, 1 A 250 V AC, 0.2 A 30 V DC, 0.2 A Min. contact capacity 100 V AC, 10 mA 5 V DC, 100 mA Symbol Name Status Description SR/SK Input logic selector SR Source logic SK [Default] Sink logic Symbol Name Status Description 485/OPE RS-485 communication/ operator selector 485 ModBus communication OPE [Default] Digital Operator (Option: 3G3AX-OP01)