3-2 Test Run Operation „ Setting the Motor Capacity Selection (H003), Motor Pole Number Selection (H004) and Motor Voltage Selection (H007) 3 Operation 3-5 Parameter No. Name Description Setting range Unit of Setting Default setting Interrupt during RUN H003 Motor capacity selection Sets the capacity of the motor connected to the Inverter. 200-V class 0.2/0.4/0.75/1.5/ 2.2/3.7/5.5/7.5 400-V class 0.4/0.75/1.5/2.2/ 3.7/5.5/7.5 kW Varies with the capacity. No H004 Motor pole number selection Sets the pole number of the motor connected to the Inverter. 2/4/6/8 Pole 4 No H007 Motor voltage selection Sets the voltage of the motor connected to the Inverter. 00: 200 V 01:
400 V Depends on the Inverter model No Key sequence Display example Description bk-k-k- Press the Mode key twice to display the mode selection. hk-k-k- Use the Increment or Decrement key to display "H---". hk0k0k3 Press the Mode key. "H003" is displayed. 0.2k0 Press the Mode key. The set value in "H003" is displayed. 0.4k0 Use the Increment or Decrement key to set the rated motor capacity. 0.4k0 Press the Enter key. The set value is entered. (In approx. 1 s) hk0k0k3 The parameter number is displayed again.