omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. 3-26 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page RUN mode, Acceleration/Deceleration functions A092 Acceleration time 2 0.01 to 99.99 100.0 to 999.9 1000. to 3000. 15.00 Yes s 4-22 A292 *2nd acceleration time 2 15.00 A093 Deceleration time 2 0.01 to 99.99 100.0 to 999.9 1000. to 3000. 15.00 Yes s 4-22 A293 *2nd deceleration time 2 15.00 A094 2-step acceleration/ deceleration selection 00: Switched via multi-function input 09 (2CH) 01:

Switched by setting 00 No  4-22 A294 *2nd 2-step acceleration/ deceleration selection 00 A095 2-step acceleration frequency 0.0 to 400.0 0.0 No Hz 4-22 A295 *2nd 2-step acceleration frequency 0.0 A096 2-step deceleration frequency 0.0 to 400.0 0.0 No Hz 4-22 A296 *2nd 2-step deceleration frequency 0.0 A097 Acceleration pattern selection 00: Line 01: S-shape curve 00 No  4-23 A098 Deceleration pattern selection 00: Line 01: S-shape curve 00 No  4-23 External frequency adjustment A101 FI start frequency 0.0 to 400.0 0.0 No Hz 4-10 A102 FI end frequency 0.0 to 400.0 0.0 No Hz 4-10 A103 FI start ratio 0. to 100. 0. No % 4-10 A104 FI end ratio 0. to 100. 100.

No % 4-10 A105 FI start selection 00: Use FI start frequency [A101] 01: 0 Hz start 01 No  4-10