omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. 3-33 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page Others C091 Not used Use "00". * Do not change. 00    C101 UP/DWN selection 00: Do not store the frequency data 01: Store the frequency data 00 No  4-50 C102 Reset selection 00: Trip reset at power-on 01: Trip reset when the power is OFF 02: Enabled only during trip (Reset when the power is ON.) 00 No  4-48 C141 Logic operation function A input 00: RUN (signal during RUN) 01: FA1 (constant speed arrival signal) 02:

FA2 (over set frequency arrival signal) 03: OL (overload warning) 04: OD (excessive PID deviation) 05: AL (alarm output) 06: Dc (disconnection detected) 07: FBV (PID FB value fault) 08: NDc (network error) 10: ODC (communication option disconnected) 00 No  4-59 C142 Logic operation function B input 01 No  4-59 C143 Logic operator selection 00: AND 01: OR 02:

XOR 00 No  4-59 C144 Output terminal P1 ON delay 0.0 to 100.0 0.0 No s 4-60 C145 Output terminal P1 OFF delay 0.0 to 100.0 0.0 No s 4-60 C146 Output terminal P2 ON delay 0.0 to 100.0 0.0 No s 4-60 C147 Output terminal P2 OFF delay 0.0 to 100.0 0.0 No s 4-60 C148 Relay output ON delay 0.0 to 100.0 0.0 No s 4-60 C149 Relay output OFF delay 0.0 to 100.0 0.0 No s 4-60