4-1 Monitor Mode Multi-function Input Monitor [d005] •The LED lighting position indicates the input status of the multi-function input terminals. •The item that the built-in CPU recognizes to be "significant" is indicated as being ON. This does not depend on the NO/NC contact setting. (Example) FW, Multi-function input terminals S7, S2, S1: ON Multi-function input terminals S8, S6, S5, S4, S3: OFF ON Display ON OFF : ON : OFF OFF Multi-function input terminals S8 S7 S6 S5 S4 S3 S2 S1 (OFF) (ON)(OFF)(OFF)(OFF)(OFF)(ON) (ON) 4 Multi-function Output Monitor [d006] Functions •The LED lighting position indicates the output status of the multi-function output terminals.
•This monitor displays the output status of the built-in CPU, not the control circuit terminal status. (Example) Multi-function output terminals P2, P1: ON Relay output terminal MA, Multi-function output terminals P5, P4, P3: OFF Display ON OFF : ON : OFF Multi-function output terminals Relay output terminals MA P5 P4 P3 P2 P1 (OFF)(OFF)(OFF) (OFF)(ON) (ON) Output Frequency Monitor (After Conversion) [d007] Displays a gain conversion value based on the coefficient set in frequency conversion coefficient b086. This monitor is used to change the unit of displayed data (e.g. motor rpm).
"d007 display" = "Output frequency (d001)" Ч "Frequency conversion coefficient (b086)" (b086) 0.1 to 99.9 (Can be set in increments of 0.1.) (Example) To display 4-pole motor rpm: Motor rpm N (min -1 ) = (120 Ч f (Hz)) / P (pole) = f (Hz) Ч 30 As such, when b086 = 30.0, a motor rpm of 1800 (60 Ч 30.0) is displayed. (Display) 0.00 to 99.99 : Displays in increments of 0.01. 100.0 to 999.9 : Displays in increments of 0.1. 100. to 9999. : Displays in increments of 1. 1000 to 3996 : Displays in increments of 10. 4-2