4-2 Function Mode RUN Command Selection Select the method for using the RUN/STOP command. 4 Functions Base Frequency •Match the Inverter output (frequency/voltage) to the motor rating. Be careful, especially if you set a base frequency below 50 Hz. Otherwise, the motor may burn out. * To switch to the 2nd/3rd control, allocate 08 (SET)/17 (SET3) to the desired multi-function input and then turn it on. •For the base frequency and motor voltage selections, match the Inverter output (frequency/ voltage) to the motor rating.
Output voltage Motor voltage selection (A082) Base frequency (A003/A203/A303) Output frequency (Hz) •If you apply a base frequency of over 60 Hz, a special motor is required. This may require the Inverter to increase its capacity to accommodate a different applicable motor. •Set the motor voltage selection according to the motor specifications. If the voltage exceeds the specified level, the motor may burn out. 4-11 Parameter No. Function name Data Default setting Unit A002 RUN command selection 01: Terminal 02: Digital Operator (F001) 03: ModBus communication 04: Option 1 05:
Option 2 02 Related functions F004, C001 to C008, C019 Data RUN command source 01 Turn on/off the FW or RV allocated to terminals. The STOP command is activated if both Forward/Reverse commands are input simultaneously. 02 Use the STOP/RESET key on the Digital Operator. 03 Use the Modbus communication. 04 Use option board 1. 05 Use option board 2. Parameter No. Function name Data Default setting Unit A003 Base frequency 30 to Max. frequency [A004] 60.0 Hz A203 *2nd base frequency 30 to 2nd max. frequency [A204] A303 *3rd base frequency 30 to 3rd max. frequency [A304] Related functions A004, A204, A304, A081, A082