4-2 Function Mode (Example 1) A015/A105: 00 (Example 2) A015/A105: 01 Max. frequency Max. frequency A012/A102 A012/A102 A011/A101 A011/A101 4 A013/A103 0 A014/A104 100% Analog input (0 V/0 mA) (10 V/20 mA) (0/OI) A013/A103 0 A014/A104 100% Analog input (0 V/0 mA) (10 V/20 mA) (0/OI) Functions „ Adjusting the FE-FC Terminal * Below is the ratio from -10 to 10 V. -10 to 0 V: -100% to 0% 0 to 10 V: 0% to 100% • For example, to input voltage ranging from -5 to 5 V on the FE-FC terminal, set A113 to -50%, and A114 to 50%. FV, FE, FI Sampling •You can set the built-in filter applied to frequency setting signals of the external voltage/current input.
•Helps remove noise in the frequency setting circuit. 4-15 Parameter No. Function name Data Default setting Unit A111 FE start frequency -400. to 400. (Set a start frequency.) -400. to 400. (Set an end frequency.) 0.00 Hz A112 FE end frequency 0.00 A113 FE start ratio -100. to 100.: (Set a start ratio relative to an external frequency reference of -10 to 10 V. *) -100. to 100.: (Set an end ratio relative to an external frequency reference of -10 to 10 V. *) -100. % A114 FE end ratio 100. Related functions A003, A203, A303, A081, A082 (Example 3) Forward max. frequency A112 (-10 V) -100% A113 A114 100% Analog input A111 (+10 V) (02) Reverse max. frequency Parameter No.
Function name Data Default setting Unit A016 FV, FE, FI sampling 1. to 30./31. 31. Time Related functions A011 to A016, C001 to C008