4-2 Function Mode •Select an acceleration/deceleration time switching method from the following three: Switching via a multi-function input Automatic switching at a specified frequency Automatic switching only when switching between forward/reverse If the 3rd control function is selected, however, switching by the 2-step acceleration/deceleration frequency is disabled. •To switch via a multi-function input, allocate 09 (2CH) to any of C001 to C008.
(Example 1) When A094/A294 is set to 00 (Example 2) When A094/A294 is set to 01 FW FW 2CH 4 Acceleration 2 Deceleration 2 A095/A295 A096/A296 Functions Output frequency Output frequency Acceleration 1 Deceleration 1 Acceleration time 1 Acceleration time 2 Deceleration time 2 Deceleration time 1 Acceleration Acceleration Deceleration Deceleration F002/F202/ F302 A092/ A292/ A392 A093/A293/ A393 F003/F203/ F303 F002/F202 A092/ A292 A093/ A293 F003/F203 time 1 time 2 time 2 time 1 (Example 3) When A094/A294 is set to 02 Acceleration/Deceleration Pattern •Acceleration/deceleration pattern can be set for each system.
4-38 FW 2CH Acceleration Deceleration time 2 time 1 A092/A292/ F003/F203/ A392 F303 Output frequency Acceleration Deceleration time 1 time 2 F002/F202/ A093/A293/ F302 A393 Deceleration time 1 F003/F203/ F303 Parameter No. Function name Data Default setting Unit A097 Acceleration pattern selection 00: Line 01: S-shape curve 02: U-shape curve 03: Inverted U-shape curve 04: EL-S-shape curve 00 A098 Deceleration pattern selection