omron — RUN Time/Power ON Time Exceeded

4-2 Function Mode 4 Functions Soft Lock Function •You can set whether to enable or disable the writing of various code data. This helps prevent data rewriting due to erroneous operation. •Select the soft lock setting and performing method from the above table. •To use a multi-function input terminal, allocate 15 (SFT) to any of multi-function inputs 1 to 8 (C001 to C008). RUN Time/Power ON Time Exceeded •If the total RUN time of the Inverter exceeds the time set in ON time setting b034, a RUN/Power ON 'time exceeded' (RNT/ONT) signal is output.

4-51 Output frequency Desired Actual acceleration after suppression operation Time Output current Suppression level (about 160% of the rating) Time Desired Actual acceleration after suppression operation Time Parameter No. Function name Data Default setting Unit b031 Soft lock selection 00: Data other than b031 cannot be changed when terminal SFT is ON. 01: Data other than b031 and specified frequency parameter cannot be changed when terminal SFT is ON. 02: Data other than b031 cannot be changed. 03: Data other than b031 and specified frequency parameter cannot be changed. 10: Data other than parameters changeable during operation cannot be changed.

01  Related functions C001 to C008, SFT input Parameter No. Function name Data Default setting Unit b034 RUN time/Power ON time setting 0.: Does not operate. 0  1. to 9999.: Set in increments of 10 hours. 1000 to 6553: Set in increments of 100 hours. (100000 to 655300 hours) Related functions C021 to C025, C026, d016, d017