4-2 Function Mode (3) Initialization completes when "d001" appears on the monitor. Check that the data is initialized. 4 Functions Note: You cannot initialize analog input adjustments C081, C082, C083, C121, C122, and C123, as well as thermistor adjustment C085. STOP Key Selection •When "control circuit terminal block" is selected for the RUN command, you can set whether the STOP/RESET key on the Digital Operator is used to activate the STOP command and trip reset operation. •This setting is enabled when any item other than "02" (Digital Operator) is selected in RUN command selection A002.
(Refer to "RUN Command Selection" (page 4-11).) If "02" (Digital Operator) is selected in A002, the STOP command and trip reset operation are enabled regardless of this setting. 4-67 Parameter No. Function name Data Default setting Unit b087 STOP key selection 00: Enabled 01: Disabled 02: Disabled only during stop 00 Data STOP command via the STOP/ RESET key on the Digital Operator Trip reset operation via the STOP/ RESET key on the Digital Operator 00 Enabled Enabled 01 Disabled Disabled 02 Disabled Enabled