4-4 Communication Function * Allowable parameter ranges are from F002, A001, b001, C001, H003, and P001. (For F001, use command 01.) •Response frame Positive response Frame format 4 Functions * If the data is a selected item, the corresponding code data is received/transmitted. Data on H003 and H203 (motor capacity selection) are the following code data. •If the data is a numeric value, refer to the function code list. (Example) When acceleration time F002 is set to 30.00 sec, the data is "3000". Negative response: Refer to page 4-151. 4-148 STX Station No. ACK Data BCC CR Description Data size Setting STX Control code (Start of TeXt) 1 byte STX (0x02) Station No. Station No.
of the target Inverter 2 bytes 01 to 32 ACK Control code (ACKnowledge) 1 byte ACK (0x06) Data Data (Decimal ASCII code) 8 bytes * BCC Block check code 2 bytes Exclusive OR from station No. to data. (Refer to page 4-153.) CR Control code (Carriage Return) 1 byte CR (0x0D) Code data 00 01 02 03 04 05 06 07 08 09 10 Domestic/USA mode (b085 = 00 or 02) 0.2 kW 0.4 0.75 1.5 2.2 3.7 EU mode (b085 = 01) 0.2 kW 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4.0 Code data 11 12 13 14 15 16 17 18 19 20 21 Domestic/USA mode (b085 = 00 or 02) 5.5 kW 7.5 11 15 18.5 22 30 37 45 55 75 EU mode (b085 = 01) 5.5 kW 7.5 11 15 18.5 22 30 37 45 55 75