omron — Modbus-RTU Method

4-4 Communication Function 4 Functions 4-183 Register No. Function name Function code R/W Monitor and setting parameters Resolution 12BCh EL-S-curve ratio 2 during deceleration A153 R/W 0 to 50 1 [%] 12BDh to 1300h Not used    1301h Retry selection b001 R/W 0: Trip 1: 0-Hz start 2: Frequency matching start 3: Trip after frequency matching deceleration stop 4: Frequency pull-in restart  1302h Allowable momentary power interruption time b002 R/W 3 to 250 0.1 [s] 1303h Retry wait time b003 R/W 3 to 1000 0.1 [s] 1304h Momentary power interruption/undervoltage trip during stop selection b004 R/W 0: Disabled 1: Enabled 2:

Disabled during stop and deceleration stop  1305h Momentary power interruption retry time selection b005 R/W 0: 16 times 1: No limit  1306h Input phase loss protection selection b006 R/W 0: Disabled 1: Enabled  1307h Frequency matching lower limit frequency setting b007 (HIGH) R/W 0 to 40000 0.01 [Hz] 1308h b007 (LOW) R/W 1309h Trip retry selection b008 R/W 0: Trip 1: 0-Hz start 2: Frequency matching start 3: Trip after frequency matching deceleration stop 4: Frequency pull-in restart  130Ah Undervoltage retry time selection b009 R/W 0: 16 times 1:

No limit  130Bh Overvoltage/overcurrent retry time selection b010 R/W 1 to 3  130Ch Trip retry wait time b011 R/W 3 to 1000 0.1 [s] 130Dh Electronic thermal level b012 R/W 200 to 1000 0.1 [%] 130Eh Electronic thermal characteristics selection b013 R/W 0: Reduction characteristics 1: Constant torque characteristics 2: Free setting  130Fh Not used    1310h Free setting, electronic thermal frequency 1 b015 R/W 0 to 400 1 [Hz] 1311h Free setting, electronic thermal current 1 b016 R/W 0 to Rated current 0.1 [A]