omron — Standard Connection Diagram

2-2 Wiring 2 Design Continued to the next page 2-7 Terminal symbol Terminal name Description Specifications Analog Monitor output AM Multi-function analog output (Voltage) This terminal outputs a signal selected from the "0 to 10 V DC Voltage Output" monitor items: Output frequency, Output current, Output torque (with/without sign), Output voltage, Input power, Electronic thermal load rate, LAD frequency, Motor temperature, and Fin temperature. Allowable max. current: 2 mA AMI Multi-function analog output (Current) This terminal outputs a signal selected from the "4 to 20 mA DC Current Output" monitor items:

Output frequency, Output current, Output torque (without sign), Output voltage, Input power, Electronic thermal load rate, LAD frequency, Motor temperature, and Fin temperature. Allowable load impedance: 250 Ω max. Digital (contact) Monitor output MP Multi-function digital output This terminal outputs a signal selected from the "0 to 10 V DC Voltage Output (PWM)" monitor items: Output frequency, Output current, Output torque (without sign), Output voltage, Input power, Electronic thermal load rate, LAD frequency, Motor temperature, Fin temperature, Digital output frequency, and Digital current monitor.

"Digital output frequency", and "Digital current monitor" output a digital pulse at 0/10 V DC pulse voltage and 50% duty ratio. Allowable max. current: 1.2 mA Max. frequency: 3.6 kHz Power supply P24 Internal 24 V DC 24 V DC power supply for contact input signal. When the source logic is selected, this terminal functions as the contact input common terminal. Allowable max. output current: 100 mA SC Input common Common terminal for the interface power supply P24 terminal, thermistor input TH terminal and digital monitor MP terminal. When the sink logic is selected, this terminal functions as the contact input common terminal. Do not connect this terminal to the ground.