omron — Extended Function Mode

Appendix-1 Parameter List Appendix * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. App-12 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Set value Acceleration/Deceleration A150 EL-S-curve ratio 1 during acceleration 0. to 50. 25. No % A151 EL-S-curve ratio 2 during acceleration 0. to 50. 25. No % A152 EL-S-curve ratio 1 during deceleration 0. to 50. 25. No % A153 EL-S-curve ratio 2 during deceleration 0. to 50. 25. No % Momentary power interruption/Trip restart b001 Retry selection 00: Alarm 01: 0 Hz start 02: Frequency matching start 03:

Trip after frequency matching deceleration stop 04: Frequency pull-in restart 00 No  b002 Allowable momentary power interruption time 0.3 to 25.0 1.0 No s b003 Retry wait time 0.3 to 100.0 1.0 No s b004 Momentary power interruption/ undervoltage trip during stop selection 00: Disabled 01: Enabled 02: Disabled during stop and deceleration stop 00 No  b005 Momentary power interruption retry time selection 00: 16 times 01: No limit 00 No  Momentary power interruption/Trip restart b006 Input phase loss protection selection 00: Disabled 01: Enabled 00 No  b007 Frequency matching lower limit frequency setting 0.00 to 99.99 100.0 to 400.0 0.00 No Hz b008 Trip retry selection 00: Trip 01:

0 Hz start 02: Frequency matching start 03: Trip after frequency matching deceleration stop 04: Frequency pull-in restart 00 No  b009 Undervoltage retry time selection 00: 16 times 01: No limit 00 No  b010 Overvoltage/ overcurrent retry time selection 1 to 3 3 No Time b011 Trip retry wait time 0.3 to 100.0 1.0 No s