Appendix-1 Parameter List Appendix * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. App-25 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Set value Multi-function output terminal C031 Multi-function output terminal P1 contact selection 00: NO contact at MA; NC contact at MB 01:
NC contact at MA; NO contact at MB 00 No C032 Multi-function output terminal P2 contact selection C033 Multi-function output terminal P3 contact selection C034 Multi-function output terminal P4 contact selection C035 Multi-function output terminal P5 contact selection C036 Relay output (MA, MB) contact selection 01 Level and output terminal status C038 Light load signal output mode 00: Enabled during acceleration/deceleration/ constant speed 01: Enabled only during constant speed 01 No C039 Light load detection level 0.0 to 2.00 × Rated current Rated current No A C040 Overload warning signal output mode 00: Enabled during acceleration/deceleration/ constant speed 01:
Enabled only during constant speed 01 No C041 Overload warning level 0.0: Does not operate. 0.1 × Rated current to 2.00 × Rated current Rated current No A C042 Arrival frequency during acceleration 0.00 to 99.99 100.0 to 400.0 0.00 No Hz C043 Arrival frequency during deceleration 0.00 to 99.99 100.0 to 400.0 0.00 No Hz C044 PID deviation excessive level 0.0 to 100.0 3.0 No % C045 Arrival frequency during acceleration 2 0.00 to 99.99 100.0 to 400.0 0.00 No Hz C046 Arrival frequency during deceleration 2 0.00 to 99.99 100.0 to 400.0 0.00 No Hz C052 PID FB upper limit 0.0 to 100.0 100.0 No % C053 PID FB lower limit 0.0 to 100.0 0.0 No %