Appendix-1 Parameter List Appendix * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. App-27 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Set value Communication function C071 Communication speed selection (Baud rate selection) 02: Loop-back test 03: 2400 bps 04: 4800 bps 05: 9600 bps 06: 19200 bps 04 No  C072 Communication station No. selection 1. to 32. 1. No  C073 Communication bit length selection 7: 7-bit 8: 8-bit 7 No  C074 Communication parity selection 00: No parity 01: Even 02: Odd 00 No  C075 Communication stop bit selection 1: 1-bit 2:

2-bit 1 No  C076 Communication error selection 00: Trip 01: Trip after deceleration stop 02: Ignore 03: Free-run stop 04: Deceleration stop 02 No  C077 Communication error timeout 0.00 to 99.99 0.00 No s C078 Communication wait time 0. to 1000. 0. No ms C079 Communication method selection 00: ASCII 01: Modbus-RTU 01 No  Adjustment C081 FV adjustment 0. to 9999. 1000 to 6553 (10000 to 65530) Factory default Yes  C082 FI adjustment 0. to 9999. 1000 to 6553 (10000 to 65530) Factory default Yes  C083 FE adjustment 0. to 9999. 1000 to 6553 (10000 to 65530) Factory default Yes  C085 Thermistor adjustment 0.0 to 999.9 1000. Factory default Yes  C091 Not used Use "00". * Do not change.

00 No  Others C101 UP/DWN selection 00: Do not store the frequency data 01: Store the frequency data 00 No  C102 Reset selection 00: Trip reset at power-on 01: Trip reset when the power is OFF 02: Enabled only during trip (Reset when the power is ON) 03: Trip reset only 00 Yes  C103 Reset frequency matching selection 00: 0 Hz start 01: Frequency matching start 02: Frequency pull-in restart 00 No 