omron — Alarm and Error Displays

5.3 Drive Alarms, Faults, and Errors ◆ Alarm and Error Displays ■ Faults When the drive detects a fault, the ALM indicator LEDs remain lit without flashing. If the LEDs flash, the drive has detected a minor fault or alarm. Refer to Minor Faults and Alarms on page 180 for more information. An overvoltage situation trips both faults and minor faults, therefore it is important to note whether the LEDs remain lit or if the LEDs flash. 178 OYMC TOEP C71060622-01-OY V1000 User Manual Type Drive Responses to Alarms, Faults, and Errors Tuning Errors • Tuning errors occur while performing Auto-Tuning. • When the drive detects a tuning error:

• The digital operator displays text indicating the specific error. • Multi-function contact outputs do not operate. • Motor coasts to stop. • Remove the cause of the error and repeat the Auto-Tuning process.

LED Operator Display Name Page bUS Option Communication Error 183 CE MEMOBUS/Modbus Communication Error 183 CF Control Fault 184 CoF Current Offset Fault 184 CPF02 A/D Conversion Error 184 CPF03 PWM Data Fault 184 CPF06 Drive specification mismatch during Terminal Board or Control Board replacement 184 CPF07 Terminal Board Communication Fault 185 CPF08 EEPROM Serial Communications Fault 185 CPF11 RAM Fault 185 LED Operator Display Name Page CPF22 A/D Conversion Error 186 CPF23 PWM Feedback Data Fault 187 CPF24 Drive Capacity Signal Fault 187 dEv Excessive Speed Deviation (for Simple V/f with PG) 187 EF0 Option Card External Fault 187 to EF1 to EF6 External Fault (input terminal S1 to S6) 188 FbH Excessive PID Feedback 188 FbL PID Feedback Loss 189 GF Ground Fault 189 LF Output Phase Loss 189