omron — Auto-Tuning Codes, Causes, and Possible Solutions

5.7 Auto-Tuning Fault Detection 220 OYMC TOEP C71060622-01-OY V1000 User Manual Torque limit when motoring is too low (L7-01 and L7-02). • Check the settings of parameters L7-01 and L7-02). • Increase the setting. LED Operator Display Error Name Er-11 Motor Speed Fault (detected only when Auto-Tuning is enabled) Cause Possible Solutions Torque reference is too high. (Enabled in OLV only.) • Increase the acceleration time (C1-01). • Disconnect the machine from the motor, if possible. LED Operator Display Error Name Er-12 Current Detection Error Cause Possible Solutions One of the motor phases is missing (U/T1, V/T2, W/T3). Check motor wiring and correct problems.

Current exceeded the current rating of the drive. • Check the motor wiring for a short between motor lines. • If a magnetic contactor is used between motors, ensure it is on. • Replace the drive. The current is too low. Attempted Auto-Tuning without motor connected to the drive. Connect the motor and perform Auto-Tuning. Current detection signal error. Replace the drive. LED Operator Display Error Name End1 Excessive V/f Setting. Detected only during Rotational Auto-Tuning, and displayed after Auto-Tuning is complete. Cause Possible Solutions The torque reference exceeded 20% during Auto-Tuning.

• Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter that data to T1-03 through T1-05. • Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning. • If possible, disconnect the motor from the load and perform Auto-Tuning. The results from Auto-Tuning the no-load current exceeded 80%. LED Operator Display Error Name End2 Motor Iron-Core Saturation Coefficient. Detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is complete. Cause Possible Solutions Motor data entered during Auto-Tuning was incorrect. • Motor data entered to the T1 parameters does not match the information written on the motor nameplate.

• Restart Auto-Tuning and enter the correct information. Auto-Tuning calculated values outside the parameter setting range, assigning the iron-core saturation coefficient (E2-07, - 08) a temporary value. • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Rotational Auto-Tuning.