omron — Installing a Motor Thermal Overload Relay on the Drive Output

7.4 Installing Peripheral Devices Note: Disable the motor protection function (L1-0 1 = “0”) when using an external motor thermal overload relay. The relay should shut off main power on the input side of the main circuit when triggered. ■ General Precautions when Using Thermal Overload Relays The following application precautions should be considered when using motor thermal overload relays on the output of AC drives in order to prevent nuisance trips or overheat of the motor at low speeds: 1. Low speed motor operation 2. Use of multiple motors on a single AC drive 3. Motor cable length 4.

Nuisance tripping resulting from high AC drive carrier frequency Low Speed Operation and Motor Thermal OL Relays Generally, thermal relays are applied on general-purpose motors. When general-purpose motors are driven by AC drives, the motor current is approximately 5 ~ 10% greater than if driven by the commercial power supply. In addition, the cooling capacity of a motor with a shaft-driven fan decreases when operating at low speeds so that even if the load current is within the motor rated value, motor overheating may occur. A thermal relay cannot effectively protect the motor due to the reduction of cooling at low speeds.

For this reason, apply the UL-recognized electronic thermal overload protection function built into the drive whenever possible. UL recognized electronic thermal overload function of the drive: Speed-dependent heat characteristics are simulated using data from standard motors and force-ventilated motors. The motor is protected from overload using this function. Using One Drive with Multiple Motors Turn off the electronic thermal overload function. Please refer to the appropriate product instruction manual to determine which parameter disables this function. The UL recognized electronic thermal overload function of the drive cannot be applied when using multiple motors on one drive!

Long motor cables When long motor cables and high carrier frequency are being used, nuisance tripping of the thermal relay may occur due to increased leakage current. Therefore, reduce the carrier frequency or increase the tripping level of the thermal overload relay. Nuisance Tripping Resulting from High AC Drive Carrier Frequency Current waveforms generated by high carrier frequency PWM drives tend to create additional temperature rise in overload relays. Therefore, it may be necessary to increase the trip level setting when encountering nuisance triggering of the relay. WARNING! Risk of Fire.

Confirm an actual motor overload condition is not present prior to increasing the thermal OL trip setting. Check local electrical codes before making adjustments to motor thermal overload settings. 272 OYMC TOEP C71060622-01-OY V1000 User Manual