omron — H Parameters: Multi-Function Terminals

B.2 Parameter Table 326 OYMC TOEP C71060622-01-OY V1000 User Manual H1 Multi-Function Digital Input Selections H1- Setting Function Description Control Mode Pg. V/f OL V PM 6 Jog Reference Selection Open: Selected speed reference Closed: Jog Frequency reference (d1-17). Jog has priority over all other reference sources. O O O — 7 Accel/Decel Time 1 Used to switch between Accel/Decel. Time 1/2 O O O — 8 Baseblock Command (N.O.) Open: Normal operation Closed: No drive output O O O — 9 Baseblock Command (N.C.) Open: No drive output Closed: Normal operation O O O — A Accel/Decel Ramp Hold Closed: The drive pauses during acceleration or deceleration and maintains the output frequency.

O O O — B Drive Overheat Alarm (OH2) Closed: Displays an OH2 alarm O O O — C Terminal A2 Enable Open: Terminal A2 disabled Closed: Terminal A2 enabled O O O — F Not used Select this setting when not using the terminal or when using the terminal in a pass-through mode. O O O — 10 Up Command Open: Maintains the current frequency reference Closed: Increases or decreases the current frequency reference. Ensure that the increase and decrease commands are set in conjunction with one another. The frequency reference source must be set to operator (b1-01 = 0). O O O — 11 Down Command O O O — 12 Forward Jog Closed: Runs forward at the Jog Frequency d1-17. O O O — 13 Reverse Jog Closed:

Runs reverse at the Jog Frequency d1-17. O O O — 14 Fault Reset Closed: Resets faults if the cause is cleared and the Run command is removed. O O O — 15 Fast-Stop (N.O.) Closed: Decelerates at the Fast-Stop time C1-09. To restart the Fast-Stop input must be released and Run must be cycled. O O O — 16 Motor 2 Selection Open: Motor 1 (E1- , E2- ) Closed: Motor 2 (E3- , E4- ) O O O — 17 Fast-stop (N.C.) Open: Decelerates according to C1-09 (Fast-stop Time) O O O — 18 Timer Input Function Set the timer delay using parameters b4-01 and b4-02. Ensure this function is set in conjunction with the multi- function output timer (H2-†† = 12). O O O — 19 PID Disable Closed:

PID control disabled O O O — 1A Accel/Decel Time Selection 2 Switches Accel/Decel times. O O O —