B.2 Parameter Table Default setting value is dependent on parameter E1-01, Input Voltage Setting. Default setting value is dependent on parameter o1-03, Digital Operator Display Selection. Default setting value is dependent on parameter o2-04, Drive Unit Selection. Parameter can be changed during run. 356 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M o2-09 Initialization mode Changes some parameter default settings depending on the region. 0: Japan 1: America 2: Europe 3: China 0 to 3 dep. on drive spec. A A A 50D — o4: Maintenance Period Use o4 parameters to perform maintenance.
o4-01 Accumulated Operation Time Setting Sets the starting value for the cumulative operation time of the drive in units of 10h. 0 to 9999 0 A A A 50B — o4-02 Accumulated Operation Time Selection Sets this parameter to log the cumulative operation time (U4-01). 0: Logs power-on time 1: Logs operation time when the drive output is active (output operation time). 0 to 1 0 A A A 50C — o4-03 Cooling Fan Operation Time Setting Used to resets the Cooling Fan operation time counter U1-04. 0 to 9999 0 A A A 50E — o4-05 Capacitor Maintenance Setting Resets the capacitor maintenance time monitor U4-05.
0 to 150 0% A A A 51D — o4-07 Inrush Prevention Relay Maintenance Setting Resets the Inrush Prevention Relay Maintenance monitor U4-06. 0 to 150 0% A A A 523 — o4-09 IGBT Maintenance Setting Resets the counter that logs the IGBTs usage time. Refer to U4-07 (IGBT Maintenance). 0 to 150 0% A A A 525 — o4-11 U2, U3 Initialize Selection Selects if U2- (Fault Trace), U3- (Fault History) monitors are reset at drive initialization. 0: Saves the fault monitor data 1: Resets the fault monitor data 0 to 1 0 A A A 510 — o4-12 kWh Monitor Initialize Selection Selects if U4-10 and U4-11 (kWh monitor) are reset at drive initialization. 0: Saves the U4-10 and U4-11 monitor data. 1:
Resets the U4-10 and U4-11 monitor data. 0 to 1 0 A A A 512 — o4-13 Number of Run Commands Initialize Selection Selects if the Run command counter (U4-02) is reset at drive initialization. 0: Saves the number of Run commands 1: Resets the number of Run commands 0 to 1 0 A A A 528 —