omron — UL Standards Compliance

D.3 UL Standards D.3 UL Standards The UL/cUL mark applies to products in the United States and Canada indicates that UL has performed product testing and evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL certification, all components inside that product must also receive UL certification. Figure D.7 UL C R US LISTED Figure D.7 UL/cUL Mark ◆ UL Standards Compliance This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The following conditions must be met to maintain compliance when using this drive in combination with other equipment:

■ Installation Area Do not install the drive to an area greater than pollution severity 2 (UL standard). ■ Main Circuit Terminal Wiring OYMC recommends using UL-listed copper wires (rated at 75 ° C) and closed-loop connectors or CSA-certified ring connectors sized for the selected wire gauge to maintain proper clearances when wiring the drive. Use the correct crimp tool to install connectors per manufacturer recommendation. Table D.4 lists a suitable closed-loop connector manufactured by JST Corporation.

Table D.4 Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V) 410 OYMC TOEP C71060622-01-OY V1000 User Manual Wire Gauge mm2 (AWG) Terminal Screws Crimp Terminal Model Numbers Tightening Torque N m (lb. to in.) 0.75 (18) M3.5 R1.25-3.5 0.8 to 1.0 (7.1 to 8.9) M4 R1.25-4 1.2 to 1.5 (10.6 to 13.3) 1.25 (16) M3.5 R1.25-3.5 0.8 to 1.0 (7.1 to 8.9) M4 R1.25-4 1.2 to 1.5 (10.6 to 13.3)