D.4 Safe Disable Input Precautions ■ Installation Precautions 1. To assure, that the Safe Disable function appropriately fulfills the safety requirements of the application, a throughout risk assessment for the whole safety system has to be carried out. 2. If only one signal line from the safety device to the drive is used (H1 and H2 are linked at the drive), the drive must be installed in an enclosure with protection degree of at least IP54 in order to maintain EN954-1, safety category 3 compliance. If two separate signal lines from the safety device to the inputs H1 and H2 are used (like shown above), the drive must not necessarily be installed in an IP54 enclosure. 3.

If the safety device and the drive are installed in separate cabinets, the Safe Disable wires must be installed in a short circuit proof way. 4. The Safe Disable function does not cut the power supply to the drive and does not provide electrical isolation. Before any installation or maintenance work is done, the drives power supply must be switched off. 5. When PM motors are used, the following must be considered: Even if the Safe Disable function is active, although unlikely a failure in two of the drives power devices can occur which means that current flows through the motor winding. In an induction motor no torque can be produced by that.

However, if this happens and a PM motor is connected a torque is produced causing an alignment of the rotor magnets. The rotor may turn up to 180 deg electrically. It must be ensured, that this possible failure mode is not safety critical for the application. 6. The wiring distance for the Safe Disable inputs should be shorter than 30 m. 7. The time from opening the Safe Disable input until the drive output is switched off is less than 1 ms. Standards Compliance D OYMC TOEP C71060622-01-OY V1000 User Manual 417