omron — Three-Phase 200 V Class (VZA20P1 ~ 2015) Three-Phase 400 V Class (VZA40P2 ~ 4015)

3.3 Main Circuit Connection Diagram 3.3 Main Circuit Connection Diagram Refer to Figure 3.3 and Figure 3.4 for standard drive connection diagrams. Connections may vary based on drive capacity. The main circuit DC power supply powers the control circuit. NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high voltage DC potential. Improper wiring connections could result in damage to the drive. ◆ Single-Phase 200 V Class (VZAB0P1 ~ B4P0) Figure 3.3 DC reactor (option) Braking Resistor Unit (option) Jumper 㧗 1 㧗 2 B1 B2 R/L1 Drive U/T1 V/T2 W/T3 Motor Single-phase 200 Vac 㧙 S/L2 Figure 3.3 Connecting Main Circuit Terminals NOTICE:

Do not connect T/L3 terminal when using single-phase power supply input. Incorrect wiring may damage the drive. ◆ Three-Phase 200 V Class (VZA20P1 ~ 2015) Three-Phase 400 V Class (VZA40P2 ~ 4015) Figure 3.4 DC reactor (option) Braking Resistor Unit (option) Jumper 㧗 1 㧗 2 R/L1 S/L2 T/L3 Drive B1 B2 U/T1 V/T2 W/T3 Motor Three phase 200 Vac (400 Vac) 㧙 Figure 3.4 Connecting Main Circuit Terminals 54 OYMC TOEP C71060622-01-OY V1000 User Manual