omron — Terminal A2 Switch

3.9 Main Frequency Reference 3.9 Main Frequency Reference ◆ Terminal A2 Switch The main frequency reference can either be a voltage or current signal input. For voltage signals both analog inputs, A1 and A2, can be used, for current signals A2 must be used. Electrical Installation To use current input at terminal A2, set the DIP switch S1 to "I" (factory setting) and set parameter H3-09 = “2” or “3” (4-20 mA or 0-20 mA). Set parameter H3-10 = “0” (frequency reference). Note: If Terminals A1 and A2 are both set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both input values builds the frequency reference.

When using input A2 as voltage input, set the DIP switch S1 to “V” (left position) and program parameter H3-09 to “0” (0 to +10 Vdc with lower limit) or “1” (0 to +10 Vdc without lower limit).

3 Table 3.12 Frequency Reference Configurations OYMC TOEP C71060622-01-OY V1000 User Manual 75 Voltage Input Current Input Drive +V+ 201 0 m.5 V A current 0 to 10 V Main speed 2 kΩ A1frequency reference (voltage input) Main speed A2frequency reference (current input) ACFrequency reference common Drive +10.5 V +V 20 mA current Main speed 4 to 20 mA input A1 frequency reference or (voltage input) 0 to 20 mA input Main speed A2 frequency reference (current input) ACFrequency reference common Drive +V+ 201 0 m.5 V A current 0 to 10 V Main speed 2 kΩ A1frequency reference (voltage input) Main speed A2frequency reference (current input) ACFrequency reference common +V+ 201 0 m.5 V A current Main speed A1frequency reference (voltage input) Main speed A2frequency reference (current input) ACFrequency reference common 0 to 10 V