3.10 MEMOBUS/Modbus Termination 3.10 MEMOBUS/Modbus Termination DIP switch S2 controls the terminal resistance as shown in the Figure 3.26 . The OFF position is the default of the terminating resistor switch for MEMOBUS/Modbus communications. Turn the terminal resistor switch ON when the drive is the last drive in a series of slave drives. Table 3.15 MEMOBUS/Modbus Switch Settings Electrical Installation Figure 3.26 DIP Switch S2 3 OFF ON Note: Refer to the MEMOBUS/Modbus communications manual for details on MEMOBUS/Modbus.
Figure 3.26 DIP Switch S2 OYMC TOEP C71060622-01-OY V1000 User Manual 77 S2 Position Description ON Internal terminal resistance ON OFF Internal terminal resistance OFF (no terminal resistance); default setting