omron — Keys, Displays, and LEDs

4.2 Using the Digital LED Operator Table 4.1 Keys and Displays on the LED Operator 88 OYMC TOEP C71060622-01-OY V1000 User Manual No. Display Name Function 1 Data Display Area Displays the frequency reference, parameter number, etc. 2 ESC Key Returns to the previous menu. 3 RESET Key Moves the cursor to the right. Resets the drive to clear a fault situation. 4 RUN RUN Key Starts the drive. 5 Up Arrow Key Scrolls up to select parameter numbers, setting values, etc. 6 Down Arrow Key Scrolls down to select parameter numbers, setting values, etc. 7 STOP STOP Key Stops the drive. Note: Stop priority circuit.

A fast-stop is available by pressing the STOP key when the drive detects a danger even if the drive is running by a signal from the multi-function contact input terminal (REMOTE is set). To avoid stoppage by using the STOP key, set o2-02 (STOP Key Function Selection) to 0 (Disabled). 8 ENTER Key Selects all modes, parameters, settings, etc. Selects a menu item to move from one display screen to the next. 9 LO/RE Selection Key Switches drive control between the operator (LOCAL) and the control circuit terminals (REMOTE). Note: LOCAL/REMOTE key effective during stop in drive mode.

If the digital operator could change from REMOTE to LOCAL by incorrect operation, set o2-01 (LOCAL/REMOTE Key Function Selection) to “0” (disabled) to disable LOCAL/ REMOTE key. 10 RUN Light Lit while the drive is operating the motor. 11 LO/RE Light Lit while the operator (LOCAL) is selected to run the drive.