VLT ® 2900 Series An output signal is obtained, which is proportional to the feedback value in the interval Minimum feedback, FB MIN - Maximum feedback, FB MAX (parameter 414/415). No function (NO OPERATION) [0] 0-f MAX 0-20 mA/4-20 mA. An output signal is obtained, which is proportional to the output frequency in the interval 0 - f MAX (parameter 202 Output frequency, high limit, f MAX ). External reference min.-max. 0-20 mA (ref min-max = 0-20 mA) [1] External reference min.-max. 4-20 mA (ref min-max = 4-20 mA) [2] 0 - I INV 0-20 mA/4-20 mA. An output signal is obtained, which is proportional to the output current in the interval 0 - I INV Feedback min.-max.
0-20 mA (fb min-max = 0-20 mA) [3] Feedback min.-max. 4-20 mA (fb min-max = 4-20 mA) [4] 0 - P M,N 0-20 mA/4-20 mA. An output signal is obtained, which is proportional to the present output power. 20 mA corresponds to the value set in parameter 102 Motor power, P M,N . Output frequency 0-max 0-20 mA (0-fmax = 0-20 mA) [5] Output frequency 0-max 4-20 mA (0-fmax = 4-20 mA) [6] 0 - Temp. MAX 0-20 mA/4-20 mA. An output signal is obtained, which is proportional to the present heatsink temperature. 0/4 mA corre- sponds to a heatsink temperature of less than 20 °C, and 20 mA corresponds to 100 °C.
Output current 0-I INV 0-20 mA (0-iinv = 0-20 mA) [7] Output current 0-I IINV 4-20 mA (0-iinv = 4-20 mA) [8] Output power 0-P M,N 0-20 mA (0-Pnom = 0-20 mA) [9] Programming Output power 0-P M,N 4-20 mA (0-Pnom = 4-20 mA) [10] Inverter temperature 20-100 °C 0-20 mA (TEMP 20-100 C=0-20 mA) [11] No function (no operation) [0] Unit ready (unit ready) [1] Inverter temperature 20-100 °C 4-20 mA (TEMP 20-100 C=4-20 mA) [12] Enable/no warning (enable/no warning) [2] The analogue output can be used for stating a process value. It is possible to choose two types of output sig- nals 0 - 20 mA or 4 - 20 mA.
If used as a voltage output (0 - 10 V), a pull-down re- sistor of 500 Ω must be fitted to common (terminal 55). If the output is used as a current output the resulting resistance from the equipment connected may not ex- ceed 500 Ω. Running (RUNNING) [3] Running in reference, no warning (run on ref/no warn) [4] Running, no warnings (RUNNING/NO WARNING) [5] Running in reference range, no warnings (RUN IN RANGE/ NO WARN) [6] Ready - mains voltage within range (RDY NO OVER/UNDERVOL) [7] Alarm or warning (ALARM OR WARNING) [8] No function . Is selected if the analogue output is not to be used. Current higher than current limit, par.
221 (Current limit) [9] External Ref MIN - Ref MAX 0-20 mA/4-20 mA. An output signal is obtained, which is proportional to the resulting reference value in the interval Minimum reference, Ref MIN - Maximum reference, Ref MAX (pa- rameters 204/205). Output frequency higher than f LOW par. 225 (above frequency low) [11] Alarm (ALARM) [10] Output frequency lower than f HIGH par. 226 (below frequency high) [12] Output current higher than I LOW par. 223 (above current low) [13] FB MIN -FB MAX 0-20 mA/ 4-20 mA.
= factory setting, () = display text, [] = value for use in communication via serial communication port MG.29.A3.02 - VLT ® is a registered Danfoss trademark 41 319 Analogue output terminal 42 (AO 42 FUNCTION) Value: 323 Relay output 1-3 (RELAY 1-3 FUNCT.) Value: Function: Description of choice: