Multi-axis controllers General data and operating conditions 5 5.2 Tab. 5.2-1 If EMC conditions must be met, the permissible cable lengths can be reduced. Noise emission, in cables Noise immunity (to EN 61800-3) Radio frequency Burst Surge (surge voltage) 5.2-3 EDS94SPP101 EN 3.1-04/2007 Maximum motor and feedback cable lengths in [m] (for shielded motor cable with rated mains voltage) Type Device size with encoder without encoder E94AMxE0024 E94AMxE0034 E94AMxE0044 1 50 50 E94ASxE0024 E94ASxE0034 E94AMxE0074 ... E94AMxE0244 2 ... 3 100 100 E94ASxE0044 ... E94ASxE0244 E94ASxE0324 ... E94ASxE1044 6 ... 7 100 100 E94ASxE1454 ... E94ASxE3664 8S ... 9 150 150 E94ASxE4604 ...
E94ASxE6954 10 150 150 EMC Operation on public supply systems EN 61800-3 The controllers are designed for use in an industrial environment. Operation on public networks requires measures to be taken for limiting the expected emission of radio interferences. Design ”Single Drive” Design ”Multi Drive” EN 61800-3 see Tab. 4.2-2 EMC protection requirements Depending on the filter at the central DC supply module. Electrostatic discharge (ESD) EN 61000-4-2 8 kV with air discharge, 4 kV with contact discharge against housing Cable-guided Interference (housing) EN 61000-4-6 150 kHz ... 80 MHz, 10 V/m 80 % AM (1 kHz) EN 61000-4-3 80 MHz ...
1000 MHz, 10 V/m 80 % AM (1 kHz) Power terminals and interfaces Signal interfaces Control connections EN 61000-4-4 2 kV/5 kHz EN 61000-4-4 1 kV/5 kHz EN 61000-4-4 2 kV/5 kHz Power terminals EN 61000-4-5 1.2/50 μs, 1 kV phase/phase, 2 kV phase/PE