Lenze — 6.3.2 Operation at rated mains voltage 400 V

6 6.3 6.3.2 DC power supply modules Rated data (devices for 400/500V mains) Operation at rated mains voltage 400 V Output data c Temperature in the control cabinet 100 % Permanent rated values Cycle 1 Cycle for the second-range (0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value) Cycle 2 Cycle for the minute-range (60 s overload/120 s recovery time with 75 % of the permanent rated value)  6.3-6 EDS94SPP101 EN 3.1-04/2007 Basis of the data Mains Rated voltage UDC [V] Voltage range UDC [V] Frequency range [Hz] 565 455 - 0 % ... 620 + 0 % Voltage Frequency Current [A] Number of phases Type [V] [Hz] max. +45 °C c max.

+55 °C c 565 0 (DC) 10 7.5 565 0 (DC) 36 27 565 0 (DC) 100 75 565 0 (DC) 245 184 Output current and output power 100 % Cycle 1 Cycle 2 Type IDC [A] PDC [kW] IDC [A] PDC [kW] IDC [A] PDC [kW] E94APNE0104 10 3.6 40 14.4 15 5.4 E94APNE0104 + E94AZMP0084 10 4.9 40 19.6 15 7.4 E94APNE0364 36 13.0 108 39.0 54 19.5 E94APNE0364 + E94AZMP0294 36 17.5 108 52.5 54 26.3 E94APNE1004 100 36.2 200 109 150 54.3 E94APNE1004 + E94AZMP0824 100 48.6 200 146 150 72.9 E94APNE2454 245 88.6 368 266 368 133 E94APNE2454 + E94AZMP2004 245 119 368 357 368 179