4 4.3 4.3.5 Single-axis controllers Rated data (devices for 400/500V mains) Fuses and cable cross-sections 4.3.5 Fuses and cable cross-sections 1) The data are recommendations. Other dimensioning/laying systems are possible (e.g. according to VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper leads, conductor temperature or cores, three loaded cores. 2) Use UL-approved cables, fuses and fuse holders only. UL-fuse: voltage 500 ... 600 V, tripping characteristic ”H”, ”K5” or ”CC”. 3) Universal-current sensitive earth-leakage circuit breaker.
With cable lengths > 50 m, circuit breakers may respond depending on the cable type and switching frequency. c Circuit breaker d Fuse of utilisation category gG/gL e Fuse Observe national and regional regulations 4.3-14 EDS94SPP101 EN 3.1-04/2007 Basis of the data Mains Voltage ULN [V] Voltage range ULN [V] Frequency range f [Hz] 230 ... 500 180 - 0 % ...
550 + 0 % Operation with external mains choke Type Installation according to EN 60204-1 1) Installation according to UL 2) FI 3) c d L1, L2, L3 e L1, L2, L3 Laying system B2 c F [A] [A] [mm2] [mm2] [mm2] [A] [AWG] [mA] E94ASxE0024 C10 - 1,5 1,5 - 10 16 ≥300 E94ASxE0034 C10 - 1.5 1.5 - 10 16 ≥300 E94ASxE0044 C10 - 1.5 1.5 - 10 16 ≥300 E94ASxE0074 C16 - 2.5 2.5 - 15 14 ≥300 E94ASxE0134 C20 - 2.5 2.5 - 20 12 ≥300 E94ASxE0174 C25 - 4 4 - 25 10 ≥300 E94ASxE0244 C32 - 10 6 - 40 8 ≥300