sinee — 5.5 Start and stop control

A90 series Inverter User Guide 5.2 Check list before power up Be sure to confirm the following items before turning on the power: 5.3 Confirm the status of the inverter after power up When the power is up, the inverter keypad is displayed as follows: 5.4 Note about the macro F16.00 for the industry application macro selection, according to the need to select the macro, press the Enter key to confirm. You need to select F12.14 = 1 to restore the factory value, Then the application macro is available. See Chapter 10 for details on application macros. 5.5 Start and stop control STOP RESET and M.K of keypad. Under no fault, press to enter jog forward or press RUN to enter running mode.

When the green LED above the button is on, it means that inverter is running; when the green LED above the RUN button flickers, it means that inverter is in the ramp-to-stop status. F00.02=1: Terminal Control F00.02=0: Keypad Control The start and stop of inverter will be controlled with RUN , The start/stop control terminal defined through F02.00 - F02.05 controls the start and stop of inverter; the detailed configurations of the terminal control are defined through F00.03.

27 Confirm items Contents Make sure the input supply voltage is the same as the inverter's requirements Check Power supply Make sure the power supply circuit is connected to the circuit breaker and the power cable are connected to the R, S, T terminals of the inverter wiring Make sure the inverter and the motor are properly grounded Make sure the motor is connected to the U, V, W terminals of the inverter and the phase sequence is correct. Ensure the connection is firm.

Check Motor wiring Check Brake unit and Make sure that the brake resistor and the brake unit are wired as shown in Figure 3-3 (if the dynamic brake is required) brake resistor wiring Check Control terminals Check control terminals and other control devices connected correctly, reliably wiring Check Control terminal Confirm all terminals are disabled, to prevent running from power up status Confirm the machine at no load condition and there is no dange after power up and machine running Check Mechanical load State Display Description Normal 50.00 The factory default display is digital setting 50.00Hz Fault Character or Exx format trip code When trip code is displayed, refer to Chapter 6 Trouble Shooting No.

Function Range Default Type 00.02 Command Source 0: Keypad Control 1: Terminal Control 2: Communication Control 0 〇 M. RUN