sinee — 5.6 Frequently used process parameters

A90 series Inverter User Guide 24V Forward RUN F/R Inverter Reverse RUN F/R Xi Xi stop f COM Output frequency t -f ( a ) F00.03=2 3- wire sequence wiring diagram ( b ) F04.19=0 , F00.03=2 Running sequence 24V RUN Inverter Forward /Reverse RUN RUN F/R Xi Xi F/R stop f COM Output frequency t -f ( c ) F00.03=3 3- wire sequence wiring diagram ( d ) F04.19=0 , F00.03=3 Running sequence The 3-wire sequence of A90 inverter conforms to traditional electrical control method. Please use buttons and switches as shown in the diagram correctly so as to avoid malfunctions. Figure 5-3 3-wire sequence 5.6 Frequently used process parameters 30 No.

Function Range Unit Default Type F00.01 Drive Control Mode of Motor 1 0: V/F control (VVF) 1: Sensorless Vector Control (SVC) 0 〇 F00.04 Main Frequency Source A Options 0: Digital Frequency Setting F00.07 1: AI1 2: AI2 6: Main Frequency Communication Percentage Setting 7:

Main Frequency Communication Direct Setting 0 〇 F00.07 Digital Frequency Setting 0.00 Hz - Maximum Frequency F00.16 Hz 50.00 ● F00.14 Acceleration Time 1 0.00~650.00(F15.13=0) s 15.00 ● F00.15 Deceleration Time 1 0.00~650.00(F15.13=0) s 15.00 ● F00.16 Maximum Frequency 1.00~600.00 Hz 50.00 〇 F00.18 Upper Limit Frequency Lower Limit Frequency F00.19 - Maximum Frequency F00.16 Hz 50.00 ● F00.19 Lower Limit Frequency 0.00 - Upper Limit Frequency F00.18 Hz 0.00 ●