A90 series Inverter User Guide 62 F15.09 Acceleration/Deceleration Time Reference Frequency 0: Maximum Frequency F00.16 1: 50.00Hz 0 〇 F15.10 Automatic Switching Acceleration and Deceleration Time 0: Disabled 1: Enabled 0 〇 F15.11 Switching Frequency between Acceleration Time 1 and Acceleration Time 2 0.00 - Maximum Frequency F00.16 Hz 0.00 ● F15.12 Switching Frequency between Deceleration Time 1 and Deceleration Time 2 0.00 - Maximum Frequency F00.16 Hz 0.00 ● F15.13 Acceleration/Deceleration Time Unit 0: 0.01s 1: 0.1s 2:1s 0 〇 F15.14 Skip Frequency Point 1 0.00 - 600.00 Hz 600.00 ● F15.15 Frequency Skip Range 1 0.00 - 20.00, 0.00:
Disabled Hz 0.00 ● F15.16 Skip Frequency Point 2 0.00 - 600.00 Hz 600.00 ● F15.17 Frequency Skip Range 2 0.00 - 20.00, 0.00: Disabled Hz 0.00 ● F15.18 Skip Frequency Point 3 0.00 - 600.00 Hz 600.00 ● F15.19 Frequency Skip Range 3 0.00 - 20.00, 0.00: Disabled Hz 0.00 ● F15.20 Frequency Arrive (FAR ) Detection Bandwidth 0.00 - 50.00 Hz 2.50 〇 F15.21 Output Frequency Detection Range FDT1 0.00 - Maximum Frequency F00.16 Hz 30.00 〇 F15.22 FDT1 Hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 〇 F15.23 Output Frequency Detection Range FDT2 0.00 - Maximum Frequency F00.16 Hz 20.00 〇 F15.24 FDT2 Hysteresis -(Fmax-F15.23)~F15.23 Hz 2.00 〇 F15.25 Analog input Level Detection ADT 0: AI1 1:
AI2 0 ○ F15.26 Analog input Level Detection ADT1 0.00 - 100.00 % 20.00 ● F15.27 ADT1 Hysteresis 0.00 - F15.26 (Monotonic Downward is active) % 5.00 ● F15.28 Analog Input Level Detection ADT2 0.00 - 100.00 % 50.00 ● F15.29 ADT2 Hysteresis 0.00 - F15.28 (Monotonic Downward is active) % 5.00 ● F15.30 Dynamic Brake 0: Disabled 1: Enabled 0 〇 F15.31 Dynamic Brake Operation Voltage 110.0~140.0(380V, 100.0%=537V) % 125.0 (671V) 〇