A90 series Inverter User Guide 10 application macro 10.1 Applications macro Introduction For the following applications, according to the configuration of some customers, some parameters’ defualts were changed. After selecting the application macro and wiring according to the wiring diagram provided, customers can accomplish the application easily. Note: After seleting macro, you need select F12.14 = 1 to restore the factory value, then the application macro work. 10.2 Applicable occasions of macro 66 No.
Function Range Unit Default Type F16.00 Macro selection 0:General purpose 1:Air compressor application 2:Extrusion machine applications 3:Pump applications 4:Fan application 0 〇 Application macro Applicable occasions General purpose Keypad control running, general purpose inverter. The terminal factory configuration see Chapter III control circuit standard wiring diagram Air compressor application Air compressor control logic by the controller, inverter only works as the speed control executor. Configuration factory parameters according to 4-20mA current signal as the frequency reference. Extrusion machine applications Analog input as frequency reference, terminal control start and stop.
Can be used for extruder and feed motor control. Pump applications Contains a sleep, wake-up function of constant pressure water supply applications, can control the variable speed pump and sleep pump. Digital target pressure, 4-20mA pressure transmitter as a pressure feedback. Fan application Including manual operation/ automatic operation switch, speed tracking start, continuious woking under instantaneous power failure. This is a normal duty application. When the X2 terminal is enabled, the manual operation enabled