A90 series Inverter User Guide 10.3 Application of the corresponding wiring diagram and parameter list 10.3.1 Compressor wiring diagram and parameter list Analog input common Frequency reference Analog input : 0-10V or 4-20mA AI2 GND 24V Auxiliary power:24VDC ,≤ 100mA Coast-to-Stop RUN/STOP X1 X2 Digital input terminal Digital input terminal Fault reset X6 COM Digital input terminal Digital input common EC EB EA fault output Relay output Connect to controller the communication port A+ RS485 communication port Get Inverter running status A- The parameter list of Air compressor application macro F16.00=1 : Air compressor application , After restore the factory value , Parameters shown in the following table : 67 No.
Function range Unit Default 0: V / F control (VVF) (asynchronous Drive control mode of machine) F00.01 0 motor 1 1: Sensorless vector control (SVC) (synchronous machine) 0: Keypad control Command source F00.02 1: Terminal control 0 selection 2: communication control Main Frequency Source A F00.04 2:AI2* 2 Options F00.14 Acceleration time 1 s 25.00 F00.15 Deceleration time 1 s 30.00 F00.16 Maximum frequency Hz 50.00 F00.18 Upper limit frequency Hz 50.00 F00.19 Lower limit frequency Hz 30.00 F00.21 Reverse control 1:Prohibit Reverse 1 4.0kHz(A90-4T017B and the lower) Model F00.23 Carrier Frequency * kHz others are 2.0kHz related Automatic Adjustment of F00.24 0: Disabled 0 Carrier Wave