sinee — The parameter list of Air compressor application macro

A90 series Inverter User Guide Note 1: The above table is the asynchronous motor air compressor application parameter table,When the motor type is a synchronous motor,Please set F01.00 = 2 (permanent magnet synchronous motor), F00.01 = 1 (SVC control),F00.23 = 4.0 kHz (carrier frequency), And according to the motor parameters set F00.16 (maximum frequency), F00.18 (upper limit frequency),F00.19 (lower limit frequency). 68 0: Common Asynchronous motor 1: Inverter Asynchronous motor F01.00 Motor Type 0 2: Permanent Magnet Synchronous Motor F02.00 X1 Digital Input Function 1: Run Terminal “RUN” 1 F02.01 X2 Digital Input Function 9:

Coast to Stop 9 Minimum Input of Curve F02.37 Analog input AI2, minimum V 2.10 2 Setting Corresponding to Minimum corresponds to the frequency F02.38 Minimum Input of Curve % 0.0 ratio 2 Maximum Input of Curve F02.39 Analog input AI2 maximum V 9.90 2 Setting Corresponding to The maximum input corresponds to the F02.40 Maximum Input of Curve % 100.0 frequency ratio 2 F03.00 Y1 Output Function 1: Inverter Running 1 F03.02 R1 Output Function 7: Inverter Fault 7 F04.00 Start Mode 0: Start Directly 0 F04.19 Stop Mode 0: Ramp-To-Stop 0 F05.00 V / F curve setting 0: Straight line V / F curve 0 Motor overload protection F07.01 0.2~10.00 1.02 gain Motor overload warning F07.02 50~100 100 coefficient