sinee — A90 User Manual

User Manual of A90 Series Inverter 102 on the motor type F14.09 Stator resistance of asynchronous motor 1-60,000 (rated power of motor: ≤ 75 kW) 0.1-6,000.0 (rated power of motor: > 75kW) mΩ Depending on the motor type ○ F14.10 Rotor resistance of asynchronous motor 1-60,000 (rated power of motor: ≤ 75 kW) 0.1-6,000.0 (rated power of motor: > 75kW) mΩ Depending on the motor type ○ F14.11 Leakage inductance of asynchronous motor 0.01 to 600.00 (rated power of motor: ≤ 75 kW) 0.001 to 60.000 (rated power of motor: > 75 kW) mH Depending on the motor type ○ F14.12 Mutual inductance of asynchronous motor 0.1 to 6,000.0 (rated power of motor: ≤ 75 kW) 0.01 to 600.00 (rated power of motor:

> 75 kW) mH Depending on the motor type ○ F14.13 No-load excitation current of asynchronous motor 0.01 to 600.00 (rated power of motor: ≤ 75 kW) 0.1 to 6,000.0 (rated power of motor: > 75 kW) A Depending on the motor type ○ F14.14 Flux weakening coefficient 1 of asynchronous motor 10.00 - 100.00 % 87.00 ○ F14.15 Flux weakening coefficient 2 of asynchronous motor 10.00 - 100.00 % 80.00 ○ F14.16 Flux weakening coefficient 3 of asynchronous motor 10.00 - 100.00 % 75.00 ○ F14.17 Flux weakening coefficient 4 of asynchronous motor 10.00 - 100.00 % 72.00 ○ F14.18 Flux weakening coefficient 5 of asynchronous motor 10.00 - 100.00 % 70.00 ○ F14.19 - F14.33 Reserved F14.34 Motor parameter 0:

No operation 0 ○