User Manual of A90 Series Inverter reverse 40.00Hz. During the main and auxiliary operations, the range of the auxiliary frequency source B depends on the selected object, maximum frequency by default. If selected relative to the main frequency source A (F00.09=1), the range of the auxiliary frequency source B will change along with that of the main frequency source A (according to the maximum frequency by default). Fig. 7-3. Both the main frequency source A and the auxiliary frequency source B have a set Such parameters are mainly used to adjust the gain of each setting source, as shown in gain. When synthesis is selected via the function code F00.06, a synthetic gain will be generated.

The final setting is limited by the analog adjustment and upper and lower frequency limits. 124 Function Default Function code name Parameter description Unit Attribute code setting F00.09 Reference options of auxiliary frequency source B in main and auxiliary operation 0: relative to the maximum frequency 1: Relative to main frequency source A 0 ○ Function Default Function code name Parameter description Unit Attribute code setting F00.10 Gain of main frequency source 0.0~300.0 % 100.0 ● F00.11 Gain of auxiliary frequency source 0.0~300.0 % 100.0 ● F00.12 Synthetic gain of main and auxiliary frequency sources 0.0~300.0 % 100.0 ● F00.13 Analog adjustment of synthetic frequency 0:

synthetic frequency of main and auxiliary channels 1: AI1 * synthetic frequency of main and auxiliary channels 2: AI2 * synthetic frequency of main and auxiliary channels 0 ○