sinee — A90 User Manual

User Manual of A90 Series Inverter the PLC process will be performed every time the inverter is started. The PLC power-down memory is to record the current simple PLC running times (F18.10), running stage (F18.11), and running time at the current stage (F18.12) before the memory is powered off. The inverter will continue to run from the memory stage when the inverter is powered on again. If you choose no memory, the PLC process will be performed every time the inverter is powered on. In order to meet different working conditions, the running time involved in the PLC function is set to a numerical value.

Its specific meaning needs to be set in conjunction with the simple PLC time unit (F08.18). At present, there are two types of unit: second and minute. 192 Default Function code Function code name Parameter description Unit Attribute setting F08.18 Simple PLC time unit 0: s (second) 1: min (minute) 0 ● Function Default setting Function code name Parameter description Unit Attribute code F08.19 Setting of the first segment Ones place: Running direction options 0: forward 1: reverse Tens place: Acceleration and deceleration time options 0: acceleration and deceleration time 1 1: acceleration and deceleration time 2 2: acceleration and deceleration time 3 3:

acceleration and deceleration time 4 0 ● F08.20 Running time of the first segment 0.0 - 6000.0 s/min 5.0 ● F08.21 Setting of the second segment Ones place: Running direction options 0: forward 1: reverse Tens place: Acceleration and deceleration time options 0 ●