User Manual of A90 Series Inverter In order to meet different needs, the inverter also supports communication timeout and response delay during the communication based on the Modbus protocol. As shown in Fig. 7-29, the communication time interval △ t is defined as the period from the previous reception of valid data frames by the slave station (inverter) to next reception of valid data frames. If △ t is greater than the set time (depending on the function code F10.03; this function is invalid if set to 0), it will be regarded communication timeout. 2# 3# 1# 1# Send Return Return Send Return Send Return △ t Fig. 7-29 Schematic Diagram of Communication Timeout Example of this function:

If the master station must send data to a slave station (e.g. #1) within a certain period, you can use the communication timeout function of #1 slave station and set F10.03>T. The communication timeout fault will not be triggered during normal communication. However, if the master station does not send data to #1 slave station within the specified time T, and this lasts for more than the set value of F10.03, a communication fault (E16) will be reported. Once informed of the “communication fault of #1 slave station”, the staff can conduct troubleshooting.

★ The set value of F10.03 must be greater than the set time T, but must not be too large, in order to avoid adverse effects arising from too long operation in the fault status. ★ F10.03 should be set to be invalid under normal circumstances. This parameter will be set only in the continuous communication system to monitor the communication. 211 Function Function Default Parameter description Unit Attribute code code name setting F10.03 Modbus communicat ion timeout 0.0 to 60.0; 0.0: invalid (also valid for master-slave mode) s 0.0 ●